A customer with a swing-gate motor wanted both openings from the phone: full, for the car, and pedestrian, one leaf. He already had the Automatic Gate Pack and a spare Shelly 1 Gen3. He got it right: exactly those two parts are needed. Here is why, and how to configure them through the API as well as the app.
One channel per input
The Shelly 1 Gen3 has a single relay, switch:0: it gives one command. A two-leaf swing gate controller has two separate command inputs, one per mode. One command per input, one Shelly per input:
| Device | Controller input | Extra |
|---|---|---|
| Shelly no. 1 (from the pack) | Full opening | Plus Add-on + limit switch: state |
| Shelly no. 2 (spare) | Pedestrian opening | — |
Wiring: dry contact in parallel
The Shelly 1 Gen3’s O and I terminals are a potential-free contact: they close together when the relay acts and carry no voltage of their own. Electrically they are a push button. So:
- Each Shelly’s O–I goes, with two wires, to its mode’s command input, in parallel with the existing push button. Remote and wall button keep working as before.
- The Shelly’s supply (L/N) is a separate circuit from the contact. Many controllers offer a 24 V auxiliary output in AC: check the Shelly’s datasheet accepts that voltage before using it; 24 V AC is not 24 V DC.
- The motor’s power never goes through the Shelly. The contact only “presses” the input; the controller still drives the motor.
Input names vary by manufacturer: full opening is often labelled “step-by-step”, “PP” or “start”, pedestrian “ped”. Confirm it in the controller’s manual before connecting.
Pulse mode: auto_off at one second
A gate controller expects a pulse, the same as a press of the button. A relay that stays closed is a button held down: depending on the controller, it locks up, ignores commands or drops into hold-to-run mode. In the app it is Auto-off at 1 s; over RPC, on each of the two devices:
http://<ip>/rpc/Switch.SetConfig?id=0&config={"auto_off":true,"auto_off_delay":1}
With that, Switch.Set with on=true gives a one-second pulse and the relay returns on its own. It is the call you would use from Home Assistant, a script or another system:
http://<ip>/rpc/Switch.Set?id=0&on=true
Check the mode of the Shelly’s SW input too: with nothing connected, set it detached (in_mode: "detached") so no noise on the terminal can fire the relay.
Why the state has to come from a sensor
The step-by-step input is sequential: each pulse cycles open → stop → close → stop. The controller knows where it is in that cycle; the Shelly does not. The relay only knows it sent a pulse, never which way the gate went. That is why the pack includes a magnetic limit switch on the no. 1’s Plus Add-on: it appears as input:100 and its state is the real position.
http://<ip>/rpc/Input.GetStatus?id=100
With that you can build automations that make sense: warn if the gate has been open more than ten minutes, or not send a “close” pulse when it is already closed — which on step-by-step would open it. To have the app show “Open/Closed” instead of a switch, see the article on the limit switch.
Safety
- Photocells across the opening and force limiting with reversal on obstruction: they belong to the controller, not the Shelly, and they must be there.
- Do not enable automatic closing without photocells.
- Make sure no scene can pulse both inputs at once: a full and a pedestrian pulse in quick succession leave the controller in a state that is hard to predict.
- A gate controller carries mains voltage and drives a heavy moving leaf. Without experience, have an installer connect it.
Frequently asked questions
Wouldn’t a two-channel Shelly 2PM do?
Its outputs are not dry contacts: they switch the phase that supplies it. A voltage-free command input needs a potential-free contact, which is what the Shelly 1 Gen3 provides.
Will the usual remote still work?
Yes. Being in parallel with the push button, remote and button carry on; the Shelly adds another way in.
In short: one Shelly 1 Gen3 per input; O–I in parallel with the push button; auto_off at 1 s on both; the state from the limit switch on input:100, never from the relay.